Program by W.G. ACKER and N.E. STRAND PLANT LOCATION SYSTEM DESCRIPTION COMBUSTION AIR SYSTEM IDENTIFICATION NUMBER 9 June 2007 3:25pm ZIMMERMAN & LAVINE CALCULATION ELEVATION ABOVE SEA LEVEL 0. FEET BAROMETRIC AIR PRESSURE 29.9210 Inches Hg. DUCTWORK OR GAGE PRESSURE 0.0000 ATMOSPHERIC TOTAL ABSOLUTE PRESSURE 29.9210 Inches Hg. TOTAL ABSOLUTE PRESSURE (32 F) 14.6960 Psia DRY BULB AIR TEMEPERATURE 70.0000 F WET BULB TEMPERATURE 54.3451 F DEW POINT TEMPERATURE 41.0116 F ADIABATIC SATURATION TEMPERATURE 53.1250 F SAT. HUMIDITY RATIO AT ADIAB. SAT. TEMP. (Ws) 0.008535 lbs w.v./lb da RELATIVE HUMIDITY 35.0000 % PERCENT SATURATION 34.4349 % ACTUAL AIR FLOW 17.8468 ACFM STANDARD AIR CONDITION-AIR FLOW 17.7618 SCFM HUMIDITY RATIO 0.005408 lbs w.v./lb da HUMIDITY RATIO GRAINS 37.8543 grns w.v./lb da SATURATION HUMIDITY RATIO (Ws) 0.015704 lbs w.v./lb da SATURATION HUMIDITY RATIO GRAINS (Ws) 109.9301 grns w.v./lb da PARTIAL PRESS OF DRY AIR IN THE MIX (Pa) 29.663096 Inches Hg. PARTIAL PRESS OF WATER VAPOR IN THE MIX (Pw) 0.257903 Inches Hg. PARTIAL PRESS: WATER VAPOR SAT. AT W.B. (Px) 0.425611 Inches Hg. PRESS: SAT. PURE WATER AT DRY BULB (Pws) 0.736867 Inches Hg. VAPOR PRESS: WATER IN MOIST AIR AT SAT. (Ps) 0.736867 Inches Hg. MOLE FRACTION OF DRY AIR-IN THE MIX. (Xa) 0.9914 moles da/mole mix MOLE FRACTION OF WATER-IN THE MIX. (Xw) 0.0086 moles wtr/mole mix MOLE FRACTION OF WATER VAPOR AT SAT. (Xws) 0.0246 mol vap/mol sat mix GAS CONSTANT OF DRY AIR IN THE MIXTURE (Ra) 53.0650 GAS CONSTANT FOR WATER VAPOR (MIXTURE) (Rw) 0.4614 GAS CONSTANT MIXTURE (R = Ra + Rw) 53.5264 MOLECULAR WEIGHT OF DRY AIR IN THE MIX. 28.7173 lb mass/mole MOLECULAR WEIGHT OF THE WATER VAPOR (MIXTURE) 0.1553 lb mass/mole MOLECULAR WEIGHT OF THE MIX. 28.8726 lb mass/mole DENSITY OF THE AIR MIXTURE 0.0746 lb wa/ft3 wa AIR SPECIFIC VOLUME 13.4696 ft3 wa/lb da AIR FLOW OF THE DRY AIR 79.4983 lbs dry air/hr WATER VAPOR FLOW 0.4299 lbs wtr vap/hr WATER VAPOR FLOW @ 100 F 0.0009 gpm AIR FLOW OF THE MIXTURE 79.9282 lbs wet air/hr ENTHALPY OF THE DRY AIR IN THE MIXTURE 9.1161 Btu/lb da ENTHALPY OF WATER VAPOR IN THE MIXTURE 5.9070 Btu/lb da TOTAL AIR MIXTURE ENTHALPY 15.0231 Btu/lb da ENTHALPY OF SATURATED STEAM (hg) 1,092.3292 Btu/lb SENSIBLE HEAT FLOW 724.71 Btu/hr LATENT HEAT FLOW 469.60 Btu/hr TOTAL HEAT FLOW 1,194.31 Btu/hr HS = 14.330355 HA = 9.116071 HWWS = 21.156143 HAS = 5.069445 Hwv = 1,092.329224 W100 = 0.004699250061