Program by W.G. ACKER and N.E. STRAND PLANT LOCATION SYSTEM DESCRIPTION HEATEDAR SYSTEM IDENTIFICATION NUMBER 9 June 2007 3:56pm ZIMMERMAN & LAVINE CALCULATION ELEVATION ABOVE SEA LEVEL 0. FEET BAROMETRIC AIR PRESSURE 29.9210 Inches Hg. DUCTWORK OR GAGE PRESSURE 0.0000 ATMOSPHERIC TOTAL ABSOLUTE PRESSURE 29.9210 Inches Hg. TOTAL ABSOLUTE PRESSURE (32 F) 14.6960 Psia DRY BULB AIR TEMEPERATURE 129.2619 F WET BULB TEMPERATURE 74.0319 F DEW POINT TEMPERATURE 41.0116 F ADIABATIC SATURATION TEMPERATURE 75.0000 F SAT. HUMIDITY RATIO AT ADIAB. SAT. TEMP. (Ws) 0.018684 lbs w.v./lb da RELATIVE HUMIDITY 5.8153 % PERCENT SATURATION 4.9964 % ACTUAL AIR FLOW 1,389.8557 ACFM STANDARD AIR CONDITION-AIR FLOW 1,244.0472 SCFM HUMIDITY RATIO 0.005408 lbs w.v./lb da HUMIDITY RATIO GRAINS 37.8543 grns w.v./lb da SATURATION HUMIDITY RATIO (Ws) 0.108233 lbs w.v./lb da SATURATION HUMIDITY RATIO GRAINS (Ws) 757.6306 grns w.v./lb da PARTIAL PRESS OF DRY AIR IN THE MIX (Pa) 29.663096 Inches Hg. PARTIAL PRESS OF WATER VAPOR IN THE MIX (Pw) 0.257903 Inches Hg. PARTIAL PRESS: WATER VAPOR SAT. AT W.B. (Px) 0.847139 Inches Hg. PRESS: SAT. PURE WATER AT DRY BULB (Pws) 4.434922 Inches Hg. VAPOR PRESS: WATER IN MOIST AIR AT SAT. (Ps) 4.434922 Inches Hg. MOLE FRACTION OF DRY AIR-IN THE MIX. (Xa) 0.9914 moles da/mole mix MOLE FRACTION OF WATER-IN THE MIX. (Xw) 0.0086 moles wtr/mole mix MOLE FRACTION OF WATER VAPOR AT SAT. (Xws) 0.1482 mol vap/mol sat mix GAS CONSTANT OF DRY AIR IN THE MIXTURE (Ra) 53.0650 GAS CONSTANT FOR WATER VAPOR (MIXTURE) (Rw) 0.4614 GAS CONSTANT MIXTURE (R = Ra + Rw) 53.5264 MOLECULAR WEIGHT OF DRY AIR IN THE MIX. 28.7173 lb mass/mole MOLECULAR WEIGHT OF THE WATER VAPOR (MIXTURE) 0.1553 lb mass/mole MOLECULAR WEIGHT OF THE MIX. 28.8726 lb mass/mole DENSITY OF THE AIR MIXTURE 0.0671 lb wa/ft3 wa AIR SPECIFIC VOLUME 14.9766 ft3 wa/lb da AIR FLOW OF THE DRY AIR 5,568.1017 lbs dry air/hr WATER VAPOR FLOW 30.1109 lbs wtr vap/hr WATER VAPOR FLOW @ 100 F 0.0606 gpm AIR FLOW OF THE MIXTURE 5,598.2126 lbs wet air/hr ENTHALPY OF THE DRY AIR IN THE MIXTURE 23.3473 Btu/lb da ENTHALPY OF WATER VAPOR IN THE MIXTURE 6.0434 Btu/lb da TOTAL AIR MIXTURE ENTHALPY 29.3907 Btu/lb da ENTHALPY OF SATURATED STEAM (hg) 1,117.5364 Btu/lb SENSIBLE HEAT FLOW 130,000.27 Btu/hr LATENT HEAT FLOW 33,650.06 Btu/hr TOTAL HEAT FLOW 163,650.33 Btu/hr HS = 30.764387 HA = 23.347324 HWWS = 43.017523 HAS = 10.315071 Hwv = 1,117.536377 W100 = 0.006154686973